Chapter 8 - Maintenance
8.8.4.11. CASE 11
Reboot controller.
If error remains, check events history in the error logger.
This signal can be activated from the CPU in case of malfunction of brakes. If it is the case:
Check ARPS and RSI, especially the brake command signals (see chapter 8.6,
page 176).
Figure 8.54
If there is no error related to the brakes, check STARC and CPU boards (see
chapter 8.9, page 232).
Problem:
(5) ShortR-EN command not activated: The safety management
task is not operational (computer). This error is displayed if the
software has detected a blocking fault on start-up. The
controller thus has no working mode, and the events history
provides details on the fault detected (invalid arm configuration,
etc.)
Solution:
?
- Controller status
- I/O
-SystemIO
- Inputs
...
26 BRK_REL_EN
...
OFF
OFF
- Outputs
...
5 BRK_EN
...
ON
ON
Arm Off
Arm On